Technical Particulars
|
Item |
Units |
Required |
Tendered |
|
|
|||
1. |
Voltage phase to phase (U to BS 6622:2007) |
kV |
33 |
33 |
2. |
Number of cores |
|
One |
One |
3. |
Conductor |
|
|
|
|
|
mm2 |
300 |
300 |
|
|
Copper |
Copper |
|
|
|
|
round |
|
|
mm |
|
20.6 |
|
|
0C |
|
≤40 |
|
4. |
Conductor screen |
|
|
|
|
|
|
|
Semi-conductive XLPE |
|
mm |
|
0.8 |
|
5. |
Insulation |
|
|
|
|
|
|
XLPE |
XLPE |
|
|
mm |
|
8.0 |
6. |
Core Screen |
|
|
|
|
|
|
|
Semi-conductive XLPE |
|
mm |
|
1.0 |
|
|
mm |
|
40.2 |
|
7. |
Metallic Layer |
|
|
|
|
|
|
|
Copper tape |
|
mm |
|
1 |
|
|
mm |
|
0.12 |
|
|
mm2 |
|
32 |
|
8. |
Metal sheath |
|
Not Applicable |
Not Applicable |
|
|
|
||
|
mm |
|||
|
mm |
|||
9. |
Lead alloy Sheath Composition |
|
||
|
|
% |
||
|
% |
|||
|
% |
|||
|
% |
|||
10. |
Aluminum Armour |
|
|
|
|
|
kPa |
|
165 |
|
|
|
172 |
|
|
|
kPa |
|
235 |
|
% |
|
99.9 |
|
|
0C |
|
25 |
|
11. |
Outer Cover |
|
|
|
|
|
|
|
PVC |
|
mm |
|
2.7 |
|
|
|
|
Additive |
|
|
|
|
Yes |
Yes |
12. |
Completed Cable |
|
|
|
|
|
mm |
|
54.4 |
|
kg |
|
5.5 |
|
|
m |
|
500 |
|
|
|
|
500 |
|
13. |
Cable Drums |
|
|
|
|
|
m |
|
2.2 |
|
m |
|
1.4 |
|
|
kg |
|
120 |
|
14. |
Conditions upon which current carrying |
|
|
|
|
Capacities laying in trefoil formation are based |
|
|
|
|
mm |
|
50 |
|
|
mm |
|
600 |
|
|
Deg. |
|
25 |
|
|
0C |
|
35 |
|
|
0C |
|
40 |
|
|
m |
|
1.2 |
|
|
|
Yes/No |
|
YES |
15. |
Maximum dielectric stress at the Sector screen (assumed smooth) |
kV/mm |
|
3.15 |
16. |
Minimum radius of bend around which can be laid |
|
|
|
|
|
m |
|
0.9 |
|
m |
|
0.9 |
|
|
m |
|
0.8 |
|
17. |
Nominal Internal diameter of pipes or ducts through which cable may be pulled. |
mm |
|
80 |
18. |
Maximum D.C Resistance of conductor per meter of cable 20 0C |
|
|
|
|
|
microhm |
|
60.1 |
|
|
microhm |
|
592 |
19. |
Maximum A.C Resistance of conductor per meter of cable at maximum conductor temperature |
microhm |
|
77.7 |
20. |
Insulation Resistance of cable per core |
|
|
|
|
|
MΩ |
|
10000 |
|
|
MΩ |
|
10000 |
21. |
Equivalent Star Reactance per meter of 3-phase Circuit at nominal frequency |
microhm |
|
0.227 |
22. |
Maximum Electrostatic capacitance per meter of cable |
pF |
|
246 |
23. |
Maximum Charging Current per core per meter of Cable at nominal voltage U0 |
A |
|
0.01 |
24. |
Current Carrying Capacity Based on the conditions specified |
|
|
|
|
Main Transformer Feeders |
A |
800 |
800 |
|
Line Feeders |
A |
400 |
400 |
25. |
Maximum Conductor Temperature |
|
|
|
|
|
0C |
|
90 |
|
|
0C |
|
90 |
|
|
0C |
|
90 |
26. |
Conductor short circuit current carrying capacity for one second, cable loaded as above prior to short circuit and final conductor temperature of 250 0C
|
kA |
25 |
25 |
27. |
Metallic layer earth faulty current Carrying Capacity for one second, cable loaded as above Prior to earth fault and final screen temperature |
kA |
16 |
16 |
0C |
|
250 |
||
28. |
Maximum dielectric loss of cable per meter of three phase circuit when laid direct in the ground at nominal voltage Uo, nominal frequency and operating oil pressure at maximum conductor Temperature |
W/m |
|
0.03 |
29. |
Maximum dielectric loss angle of charging VA of Cable when laid direct in the ground at nominal voltage ,Uo,normal frequency at |
tan d |
|
0.001 |
|
|
|
|
0.001 |
|
tan d |
|
0.001 |
|
30. |
Maximum dielectric loss angle of charging VA of cable at normal frequency conductor temperature of 20 0C at |
|
|
|
|
|
tan d |
|
0.001 |
|
tan d |
|
0.002 |
|
|
tan d |
|
0.002 |
|
31. |
Metallic layer loss (including amour if applicable) of cable per meter of three-phase circuit at nominal voltage Uo and normal frequency at the circuit rating stated above |
W |
|
5.2 |
32. |
Horizontal distance between cable supporting racks |
|
|
1000mm |
33. |
Creepage distance of sealing and porcelain |
|
|
|
|
Specified |
mm |
|
15 |
|
Guaranteed |
mm |
|
15 |
34. |
Type test certificate |
|
Yes |
Yes |
35. |
Partial discharge at 2U0 |
pC |
<=5 |
<=5 |
Cable size and structure of sections
CU/SC/XLPE/SC/CTS/PVC/AWA/PVC 1×300mm2
Construction |
Thickness (mm) |
Diameter (mm) |
1---Copper conductor |
-- |
20.6(+0.1,-0.1) |
2---Copper screen |
0.8 |
22.3 |
3---XLPE Insulation |
8.0 |
38.2(+0.5,-0.5) |
4---Insulation screen |
1.0 |
40.2 |
5---Copper tape screen |
0.12 |
40.6 |
6---PVC inner sheath |
1.4 |
43.4 |
7---Aluminum wire amour+ aluminum tape |
2.5+0.3 |
49.0 |
8---PVC outer sheath |
2.7 |
54.4(+2.0,-2.0) |