Add to Cart
XLPE / AWA / PE Middle Voltage Power Cable 19kV / 33kV 1 Core 240 mmsq UV Stabilized
S/N |
Detail |
UNITS |
DATA |
1 |
Description |
|
19/33kV 1 core 240 mmsq |
2 |
Maximum sustained conductor temperature |
oC |
90 |
3 |
Current rating (direct |
A |
469/641 |
4 |
Ground Temperature |
oC |
25 |
5 |
Ground Thermal Resistivity |
K.m/W |
1.2 |
6 |
Depth of laying |
m |
0.8 |
7 |
Method of Installation |
|
Direct Burial |
8 |
Possible Exposure to Sunlight |
Yes/No |
Yes |
9 |
Material of Conductor |
|
Copper |
10 |
Insulating material |
|
XLPE |
11 |
Number of Cores |
|
1 |
12 |
Nominal System Voltage |
kV |
19/33 |
13 |
Highest System Voltage |
kV |
36 |
14 |
Conductor size |
mm2 |
240 |
15 |
Short circuit rating |
kA for 1sec |
22.4 |
16 |
Single layer Aluminium |
Yes/No |
Yes |
17 |
Armour diameter |
|
As Per IEC 60502-2 |
18 |
Type of outer sheath |
Yes |
PE ultra violet stabilized, black |
19 |
Cable length per Drum |
|
400 |
20 |
Type of drum (wooden or |
|
|
21 |
Ageing tests required (submit |
Yes/No |
|
22 |
Previous Type Tests submitted with the bid |
Yes/No |
|
23 |
Routine Test provided on delivery |
Yes/No |
Yes |
24 |
Quality assurance |
Yes/No |
|
25 |
Operating temperature |
oC |
|
26 |
Altitude |
m |
1400 |
27 |
Relative humidity |
% |
85 |
28 |
Cable Marking: |
Yes/No |
Yes |
29 |
Applicable Standards
|
|
IEC 60502-2/SANS 1339 |