Parallel Bunched Aerial Insulated Cable
■ Product standard
Enterprise standard , Refer to“Chosen and used technical condition of parallel clustered aerial insulation cable” issued by Department of Agricultural Work , State Electric Power Corporation.
■ Application
The parallel clustered aerial insulation cable with 0.6/1kV rated voltage and below can be wide used for low voltage electric distribution system at country .This cable features good weather ability , anti-ageing , less wire loss , simple in construction , short time limit for project and can prevent effectively from electric larceny and creepage , etc phenomenon and has better safe property.
■ Operating characteristics
1. Rated voltage U0/U: 0.6/1kv
2. Max. permissible continuous temperature:
PVC,PE insulated aerial cables:70℃; XLPE insulated aerial cables:90℃
3. Max. short-circuit temperature of the conductor shall not exceed:
PVC insulated aerial cables:160℃; PE insulated aerial cables:130℃; XLPE insulated aerial cables:250℃.
4. The installation ambient temperature:
PE, XLPE≥-20℃; PVC≥0℃
■ Type of cable
Type |
Name |
BS-JKV-0.6/1 |
Rated voltage 0.6/1kV Copper-conductor , PVC insulated and Parallel bunched aerial insulated cable |
BS-JKLV-0.6/1 |
Rated voltage 0.6/1kV Aluminum-conductor , PVC insulated and Parallel bunched aerial insulated cable |
BS-JKY-0.6/1 |
Rated voltage 0.6/1kV Copper-conductor , PE insulated and Parallel bunched aerial insulated cable |
BS-JKLY-0.6/1 |
Rated voltage 0.6/1kV Aluminum-conductor , PE insulated and Parallel bunched aerial insulated cable |
BS-JKYJ-0.6/1 |
Rated voltage 0.6/1kV Copper-conductor , XLPE insulated and Parallel bunched aerial insulated cable |
BS-JKLYJ-0.6/1 |
Rated voltage 0.6/1kV Aluminum-conductor , XLPE insulated and Parallel bunched aerial insulated cable |
■ Production range of cable
Type |
No. of cores |
Rated Voltage kV |
Nominal cross-sectional mm2 |
BS-JKV,BS-JKY, BS-JKYJ |
2 |
0.6/1 |
2.5~70 |
BS-JKLV,BS-JKLY, BS-JKLYJ |
4—120 |
||
BS-JKV,BS-JKY, BS-JKYJ |
4 |
2.5~70 |
|
BS-JKLV,BS-JKLY, BS-JKLYJ |
4—70 |
||
BS-JKV,BS-JKY, BS-JKYJ |
3+1 |
6~120 |
|
BS-JKLV,BS-JKLY, BS-JKLYJ |
6—120 |
■ Construction and main technical data
BS two-core constant section of parallel clustered aerial insulated cable |
|||||||||||||||||
Number and nom. Cross-section of cond- uctors mm2 |
Min. No. of a signal wire in cond- uctor |
Diameter of Con- ductor mm |
insul- ation thic- kness mm |
Max. D.C. resis- tance of copper conductor (20℃) Ω/km |
Min. insul- ation resi- stance of rated work temp- erature Ω. km |
Single Tensile force of cable N |
Cable calculated Weight |
XLPE Cur- rent Carr-ying (40℃)A |
|||||||||
PVC insu- lated |
XLPE insul- ated |
||||||||||||||||
Kg/km |
|||||||||||||||||
Cu |
Al |
Cu |
Al |
PVC insu- lated |
XLPE insul- ated |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
||||
2×2.5 |
1 |
— |
1.78 |
1.0 |
7.41 |
— |
0.012 |
1.20 |
1914 |
— |
74 |
— |
64 |
— |
32 |
— |
|
2×4 |
1 |
1 |
2.26 |
1.0 |
4.61 |
7.39 |
0.010 |
1.00 |
3009 |
1337 |
105 |
56 |
94 |
45 |
42 |
31 |
|
2×6 |
1 |
1 |
2.76 |
1.0 |
3.08 |
4.91 |
0.007 |
0.70 |
4457 |
1927 |
146 |
72 |
133 |
59 |
49 |
40 |
|
2×10* |
6 |
6 |
3.80 |
1.0 |
1.83 |
3.08 |
0.007 |
0.67 |
6942 |
3300 |
230 |
108 |
213 |
90 |
71 |
55 |
|
2×16* |
6 |
6 |
4.80 |
1.2 |
1.15 |
1.91 |
0.007 |
0.65 |
10972 |
5024 |
363 |
165 |
337 |
139 |
97 |
75 |
|
2×25* |
6 |
6 |
6.00 |
1.2 |
0.727 |
1.20 |
0.005 |
0.54 |
16930 |
7524 |
541 |
232 |
509 |
200 |
128 |
100 |
|
2×35* |
6 |
6 |
7.00 |
1.4 |
0.524 |
0.868 |
0.005 |
0.54 |
23462 |
10354 |
751 |
319 |
709 |
276 |
158 |
122 |
|
2×50* |
6 |
6 |
8.40 |
1.4 |
0.387 |
0.641 |
0.005 |
0.46 |
33004 |
14022 |
1035 |
416 |
987 |
368 |
194 |
148 |
|
2×70* |
12 |
6 |
10.0 |
1.4 |
0.268 |
0.443 |
0.004 |
0.40 |
46922 |
20708 |
1416 |
551 |
1360 |
494 |
240 |
189 |
|
2×95* |
115 |
12 |
11.6 |
1.6 |
0.193 |
0.320 |
0.004 |
0.39 |
63518 |
27454 |
1914 |
738 |
1840 |
664 |
296 |
230 |
|
2×120* |
18 |
15 |
13.0 |
1.6 |
0.153 |
0.253 |
0.004 |
0.35 |
79822 |
34678 |
2378 |
892 |
2298 |
812 |
347 |
270 |
|
*Compacted rotundity conductor |
BS four-core constant section of parallel clustered aerial insulated cable |
|||||||||||||||||
Number and nom. Cross- section of cond- uctors mm2 |
Min. No. of a single wire in cond- uctor |
Diam- eter of Cond- uctor mm |
Insul- ation thick- ness mm |
Max. D.C. resis- tance of copper cond- uctor (20℃)Ω/km |
Min. insulation resistance of rated work temperature Ω. km |
Single Tensile force of cable N |
Cable calculated Weight |
XLPE Curr- ent Carry- ing (40℃)A |
|||||||||
PVC insul- ated |
XLPE insu- lated |
||||||||||||||||
Kg/km |
|||||||||||||||||
Cu |
Al |
Cu |
Al |
PVC insul- ated |
XLPE insul- ated |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
||||
4×2.5 |
1 |
— |
1.78 |
1.0 |
7.41 |
— |
0.012 |
1.20 |
3828 |
— |
149 |
— |
129 |
— |
29 |
— |
|
4×4 |
1 |
1 |
2.26 |
1.0 |
4.61 |
7.39 |
0.010 |
1.00 |
6050 |
2675 |
213 |
113 |
190 |
90 |
40 |
29 |
|
4×6 |
1 |
1 |
2.76 |
1.0 |
3.08 |
4.91 |
0.007 |
0.70 |
8938 |
3853 |
293 |
146 |
267 |
119 |
45 |
37 |
|
4×10* |
6 |
6 |
3.80 |
1.0 |
1.83 |
3.08 |
0.007 |
0.67 |
13884 |
6600 |
463 |
217 |
428 |
181 |
59 |
46 |
|
4×16* |
6 |
6 |
4.80 |
1.2 |
1.15 |
1.91 |
0.007 |
0.65 |
21944 |
10048 |
730 |
334 |
677 |
281 |
79 |
63 |
|
4×25* |
6 |
6 |
6.00 |
1.2 |
0.727 |
1.20 |
0.005 |
0.54 |
33860 |
15048 |
1087 |
468 |
1022 |
403 |
104 |
83 |
|
4×35* |
6 |
6 |
7.00 |
1.4 |
0.524 |
0.868 |
0.005 |
0.54 |
46924 |
20708 |
1510 |
643 |
1423 |
556 |
130 |
101 |
|
4×50* |
6 |
6 |
8.40 |
1.4 |
0.387 |
0.641 |
0.005 |
0.46 |
66008 |
28004 |
2071 |
833 |
1975 |
737 |
158 |
126 |
|
4×70* |
12 |
6 |
10.0 |
1.4 |
0.268 |
0.443 |
0.004 |
0.40 |
93844 |
41416 |
2834 |
1101 |
1101 |
979 |
202 |
158 |
|
*Compacted rotundity conductor |
3+1 cores constant section of parallel clustered aerial insulated cable |
||||||||||||||||||||
Number and nom. Cross-section of cond- uctors mm2 |
Min. No. of a single wire in conductor |
Diameter of cond- uctor mm |
Insu- lation thick- ness mm |
Max.D.C. resi- stance of copper cond- uctor (20℃) Ω/km |
Min. insulation resis- tance of rated work tempe- rature Ω. km |
Single Tensile force of cable N |
Cable calculated Weight |
XLPE Curr- ent carr- ying (40℃)A |
||||||||||||
PVC insu-lated |
XLPE insul- ated |
|||||||||||||||||||
Cu |
Al |
Kg/km |
||||||||||||||||||
Main core |
Fou- rthly core |
Main core |
Four- thly core |
Main core |
Fou- rthly core |
Main core |
Fou- rthly core |
Cu |
Al |
PVC insu- lated |
XLPE insu- lated |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
|
3×6+ 1×4 |
1 |
1 |
1 |
1 |
2.76 |
2.76 |
1.0 |
1.0 |
3.080 |
4.910 |
0.007 |
0.700 |
8190 |
3552 |
274 |
138 |
248 |
112 |
49 |
— |
3×10+ 1×6* |
6 |
1 |
6 |
1 |
3.80 |
2.76 |
1.0 |
1.0 |
1.830 |
3.080 |
0.007 |
0.670 |
13828 |
5281 |
421 |
198 |
388 |
165 |
59 |
|
3×16+ 1×10* |
6 |
6 |
6 |
6 |
4.80 |
3.80 |
1.2 |
1.2 |
1.150 |
1.910 |
0.007 |
0.650 |
19929 |
9186 |
670 |
311 |
619 |
260 |
79 |
|
3×25+ 1×16* |
6 |
6 |
6 |
6 |
6.00 |
4.80 |
1.2 |
1.2 |
0.727 |
1.200 |
0.005 |
0.540 |
30886 |
13798 |
998 |
453 |
936 |
373 |
104 |
|
3×35+ 1×25* |
6 |
6 |
6 |
6 |
7.00 |
6.00 |